Design
Glandless circulation pump with screwed connection or flange connection, EC motor with automatic power adjustment.
Application
Secondary hot water circulation systems of all kinds, hot-water heating systems of all kinds, air-conditioning, closed cooling circuits, industrial circulation systems
- Permissible temperature range
- Potable water up to 3.57 mmol/l (20 °dH): 0 °C to +80 °C
- Heating water: ‐-10 °C to +110 °C
- Mains connection 1~230 V, 50/60 Hz
- Protection class IP X4D
- Screwed connection or flange connection (depending on type) Rp 1 to DN 65
- Max. operating pressure, standard version: 6/10 bar (special version: 16 bar)
Equipment/function
Operating modes
- Manual control mode (n=constant)
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- Δp-T for temperature-controlled differential pressure (programmable via IR-Module, IR-Stick, IR-Monitor, Modbus, BACnet, LON or CAN)
Manual functions
- Operating mode setting
- Differential-pressure setpoint setting
- Setting automatic setback operation
- Pump ON/OFF setting
- Speed setting (manual control mode)
Automatic functions
- Stageless power adjustment depending on the operating mode
- Automatic setback operation
- Deblocking function
- Soft start
- Full motor protection with integrated trip electronics
External control functions
- “Overriding Off” control input (possible with Stratos IF-Modules)
- “Overriding Min” control input (possible with Stratos IF-Modules)
- “Analogue In 0 ‐ 10 V” control input (remote speed adjustment) (possible with Stratos IF-Modules)
- “Analogue In 0 ‐ 10 V” control input (remote setpoint adjustment) (possible with Stratos IF-Modules)
Signal and display functions
- Collective fault signal (potential-free NC contact)
- Individual run signal (potential-free NO contact) (possible with Stratos IF-Modules)
- Fault signal light
- LC display for indication of pump data and fault codes
Data exchange
- Infrared interface for wireless data exchange with IR-Module/IR-Stick/IR-Monitor
- Serial digital interface Modbus RTU for connection to building automation BA via BUS system RS485 (possible with IF-Modules Stratos)
- Serial digital interface BACnet MS/TP Slave for connection to building automation BA via BUS system RS485 (possible with IF-Modules Stratos)
- Serial digital interface CAN for connection to building automation BA via BUS system CAN (possible with IF-Modules Stratos)
- Serial digital LON interface for connection to a LONWorks network (possible with Stratos IF-Modules)
- Serial digital PLR interface for connection to BA via Wilo interface converter or company-specific coupling modules (possible with Stratos IF-Modules)
Dual pump management (double pump or 2 x single pump)
- Main/standby mode (automatic fault-actuated switchover/time-dependent pump cycling): Various combinations with Stratos IF-Modules (accessories) possible
- Parallel operation (efficiency-optimised peak load activation and deactivation): Various combinations with Stratos IF-Modules (accessories) possible
Equipment
- Wrench attachment point on pump body (for threaded pipe union pumps with P2≤100 W)
- In flange pumps: Flange versions
- Standard version for pumps DN 40 to DN 65: combination flange PN 6/10 (flange PN 16 according to EN 1092-2) for counter flanges PN 6 and PN 16,
- Special version for pumps DN 40 to DN 65: Flange PN 16 (according to EN 1092-2) for counter flange PN 16,
- Plug-in position for optional extension with Wilo-IF‐Modules
- Thermal insulation as standard
Materials
- Pump housing made of red brass (30/1‐12 and 40/1‐8 types, also grey cast iron)
- Impeller: Plastic
- Shaft: stainless steel
- Bearing: Carbon, synthetic resin impregnated
Scope of delivery
- Pump
- Including thermal insulation
- Including seals for threaded connection (loose)
- Including washers for flange screws (for nominal connection diameters DN 40 ‐ DN 65)
- Including installation and operating instructions
Options
- Special versions for operating pressure PN 16 (at additional charge)
Accessories
- Screwed connection for threaded connection
- Adapter fittings
- IR-Module
- IR-Stick
- IR-Monitor
- Stratos IF-Modules: Modbus, BACnet, CAN, PLR, LON, DP, Ext. Off, Ext. Min., SBM, Ext.Off/SBM